Water-cooling Antspace HK3 parameter specifications | |||
Product Overview | Input voltage | 415V±10% /60Hz /3P /N /PE | |
Total power consumption(Two power distribution cabinets share the load) | ≤1100kW | ||
Miner | Miner inlet/outlet water temperature | 35°C/45°C | |
Container | Supporting power consumption (cooling, power distribution) | 52kW | 1000kW |
Container dimension (length * width * height) |
6058mm*2438mm*2896mm | ||
Cooling tower dimension (length*width*height), | 5800mm*2240mm*4286mm(Without guardrails) | ||
Weight (container with miner weight) | 12Ton | ||
Weight(Cooling tower operating weight) | 12Ton | ||
Number of miners | 210Units | ||
Spray pump flow | 230m³/h | ||
Heat dissipation capacity | 1000kW | ||
Temperature variation between inlet and outlet(heating side)ΔT | 10° | ||
Cooling tower docking interface specifications | DN125 | ||
Heating docking interface specifications | DN100 | ||
Cooling tower inlet water pipe specifications | DN40 | ||
Cooling tower drainage pipe specifications | DN65 | ||
Heating side pressure capacity | 10Kg | ||
Design flow of heating side | 85m³/h | ||
Maximum inlet/outlet water temperature on heating side | 35℃/45℃ | ||
Heating side design ΔT | 40/50 | ||
Operating Environment Requirements | Ambient temperature | -25°C~45°C | |
Noise | 78dB(internal) / 65dB (external) | ||
Internal coolant | Specifications are selected based on local environmental conditions | ||
Water Consumption | 1.15m³/h(Water consumption of external spray, closed when the ambient temperature is below 10°C) |
The energy consumption of Antminer s19 pro hyd is 5,445 W, and the energy efficiency is 27.5 J/TH. With such a huge energy consumption, Bitmain recommends users to use their specially designed mining machine storage cabinet Antspace HK3. This container-like mining rack provides 1MW power supply can supply 210 sets of S19 PRO Hyd mining machines.
Advantages of Antspace HK3
- High-density design: 1MW heat dissipation capacity + supports up to 210 water-cooled mining machine positions for Antspace HK3 @20HC.
- Flexible heat dissipation scheme: DWT-T Dry-Wet Tower Traditional Type can be selected for Antspace HK3.
- High efficiency and energy saving: PUE is as low as 1.03; optional heating components can provide heat recovery; frequency conversion fan control reduces water consumption, energy consumption and noise for Antspace HK3.
- Intelligent control: manual/automatic dual-mode control; fully closed-loop water temperature automatic control in automatic mode keeps the mining machine in the best working condition; supports online mining machine power on/off/online program upgrade/online initiative.
- Safe and reliable: the whole system has passed cTUVus certification, and the container body has passed CCS classification society certification; condensation and leakage detection/alarm; cooling tower cage ladder and guardrail meet OSHA standards; Lock design, remote video monitoring, GPS positioning, one-button emergency stop, electric cabinet interlocking design.
- Convenient operation and maintenance: the Antspace HK3 network on both sides of the shelf is controlled by two sets of switches; each mining machine can be powered off separately; the water inlet and outlet of each mining machine can be opened and closed independently, and each has only one; The impact on other mining machines when the dimension needs to be powered on and off and taken off the shelf.
Specification for Dry-Wet Towers DWT-T and DWT-C
Product Overview | Value | |||
Type | Dry-Wet Tower Traditional Type (DWT-T) | Dry-Wet Tower Container Type (DWT-C) | ||
Dimensions(L*W*H) | 5800mm*2240mm*4200mm | 6058mm*2438mm*2896mm | ||
Heat Dissipation Capacity | 1000kw | 1000kw | ||
Outlet Temperature @ 28℃ Wet Bulb Temperature, ℃ | 35 | 35 | ||
Container Certification | None | China Classification Society Certification | ||
Safety Certification | North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012 EU Standards: EN ISO 12100, EN 60204-1 |
North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012 EU Standards: EN ISO 12100, EN 60204-1 |
||
Operating Power | 14kw~28kw | 14kw~28kw | ||
Motor Rated Voltage and Frequency | 415V±5% 60Hz(North America) 400V±5% 50Hz(EU,Middle East) |
415V±5% 60Hz(North America) 400V±5% 50Hz(EU,Middle East) |
||
Detailed Characteristics | Value | |||
Shipping Weight | 5T | 6T | ||
Operating Weight | 9T | 10T | ||
Connection Interface | DN125(GB/T 9119-2010 PN16 DN125) | DN125(GB/T 9119-2010 PN16 DN125) | ||
Water Resupply Pipe Interface | DN40(Internal thread) | DN40(Internal thread) | ||
Drain Pipe Interface | DN65(Internal thread) | DN65(Internal thread) | ||
Noise Level @25℃, 16m | 70 | 70 | ||
Water Consumption | 1m³/h~1.5m³/h | 1m³/h~1.5m³/h |